Datasheet

Relays for functional safety
Safety relays PNOZ X
PNOZ X7P
Pilz GmbH & Co. KG, Felix-Wankel-Straße 2, 73760 Ostfildern, Germany
Telephone: +49 711 3409-0, Telefax: +49 711 3409-133, E-Mail: info@pilz.com
2016-09
165
Timing diagram
[1] [2]
Legend
} Power: Supply voltage
} Start: Start circuit
} Input: Input circuit
} Output safe: Safety contacts
} [1]: Automatic start
} [2]: Manual start
} a: Input circuit closes before start circuit
} b: Start circuit closes before input circuit
} t
1
: Switch-on delay
} t
2
: Delay-on de-energisation
} t
3
: Recovery time
Installation
} The unit should be installed in a control cabinet with a protection type of at least IP54.
} Use the notch on the rear of the unit to attach it to a DIN rail.
} Ensure the unit is mounted securely on a vertical DIN rail (35 mm) by using a fixing ele-
ment (e.g. retaining bracket or an end angle).