Datasheet

Relays for functional safety
Safety relays PNOZ X
PNOZ X2.9P
Pilz GmbH & Co. KG, Felix-Wankel-Straße 2, 73760 Ostfildern, Germany
Telephone: +49 711 3409-0, Telefax: +49 711 3409-133, E-Mail: info@pilz.com
2016-09
113
Block diagram/terminal configuration
*Insulation between the non-marked area and the relay contacts: Basic insulation (over-
voltage category III), Protective separation (overvoltage category II)
Function Description
The safety relay PNOZ X2.9P provides a safety-oriented interruption of a safety circuit.
When supply voltage is supplied the "POWER" LED is lit. The unit is ready for operation
when the start circuit S12-S34 is closed.
} Input circuit is closed (e.g. E-STOP pushbutton not operated):
The LEDs "CH.1" and "CH.2" are lit.
Safety contacts 13-14, 23-24 and 33-34 are closed, auxiliary contact 41-42 is open.
The unit is active.
} Input circuit is opened (e.g. E-STOP pushbutton operated):
The LEDs "CH.1" and "CH.2" go out.
Safety contacts 13-14, 23-24 and 33-34 are opened redundantly, auxiliary contact
41-42 is closed.
Operating modes
} Single-channel operation: No redundancy in the input circuit, earth faults in the start
and input circuit are detected.
} Dual-channel operation without detection of shorts across contacts: Redundant input
circuit, detects PNOZ X2.9P
earth faults in the start and input circuit,
short circuits in the input circuit.