Commissioning
Wiring
General wiring guidelines
Note:
} Information given in the "Technical details" must be followed.
} Use copper wire that can withstand 75 °C.
} The wiring must be designed to achieve sufficient noise immunity and protection
against noise emissions in terms of EMC. Please also refer to DINEN60204-1 (Elec-
trical equipment of machines).
Inputs
} Appropriate wiring must be used to exclude short circuits between the inputs or to a
supply line!
Outputs
} If short circuits occur between the cable from the output to the load and a supply line, it
will no longer be possible to switch off the load.
Possible remedy: Exclude the error by using separate multicore cable for supply
voltages
} Use appropriate wiring to exclude short circuits between the outputs!
Pin assignment
Female connector X1 Terminal Description
A2 A2 S36 S35 S11 S11 T1 T0
x
1
A2 Reference potential for
- Device's supply voltage
- Inputs
- Fault signal and status outputs
S36 Standard input for slow shutdown, power
circuit 2
S35 Standard input for slow shutdown, power
circuit 1
S11 Voltage output 24 VDC
S11 Voltage output 24 VDC
T1 Test pulse output 1
T0 Test pulse output 0