Datasheet
Relays for functional safety
Safety relays PNOZsigma
PNOZ s30
Pilz GmbH & Co. KG, Felix-Wankel-Straße 2, 73760 Ostfildern, Germany
Telephone: +49 711 3409-0, Telefax: +49 711 3409-133, E-Mail: info@pilz.com
2016-09
873
Mechanical data 750330 751330
Stripping length with spring-loaded
terminals – 9 mm
Dimensions
Height 98,0 mm 100,0 mm
Width 45,0 mm 45,0 mm
Depth 120,0 mm 120,0 mm
Weight 410 g 410 g
Where standards are undated, the 2009-06 latest editions shall apply.
Safety characteristic data
Operating
Mode
EN ISO
13849-1:
2015
PL
EN ISO
13849-1:
2015
Category
EN 62061
SIL CL
EN 62061
PFH
D
[1/h]
IEC 61511
SIL
IEC 61511
PFD
EN ISO
13849-1:
2015
T
M
[year]
Monitoring 1
encoder PL d Cat. 2 SIL CL 2 2,34E-08 SIL 2 2,05E-03 20
Monitoring 2
encoder PL e Cat. 4 SIL CL 3 1,44E-09 SIL 3 1,21E-04 20
Monitoring
safe en-
coder PL e Cat. 4 SIL CL 3 2,78E-09 SIL 3 2,40E-04 20
All the units used within a safety function must be considered when calculating the safety
characteristic data.
The PFH value depends on the switching frequency and the load on the relay output.
If the service life graphs are not accessible, the stated PFH value can be used irrespective
of the switching frequency and the load, as the PFH value already considers the relay's
B10d value as well as the failure rates of the other components.