Datasheet
Relays for functional safety
Safety relays PNOZsigma
PNOZ s30
Pilz GmbH & Co. KG, Felix-Wankel-Straße 2, 73760 Ostfildern, Germany
Telephone: +49 711 3409-0, Telefax: +49 711 3409-133, E-Mail: info@pilz.com
2016-09
871
Times 750330 751330
Switch-on delay
With automatic start typ. 15 ms 15 ms
With automatic start max. 50 ms 50 ms
With automatic start after power
on typ. 3.920 ms 3.920 ms
With automatic start after power
on max. 4 s 4 s
With manual start typ. 40 ms 40 ms
With manual start max. 100 ms 100 ms
Delay-on de-energisation
With power failure typ. UB 240 V 100 ms 100 ms
With power failure max. UB 240
V 150 ms 150 ms
After safety function is triggered
typ. 8 ms 8 ms
After safety function is triggered
max. 15 ms 15 ms
Recovery time at max. switching
frequency 1/s
After power failure 4 s 4 s
After safety function is triggered 1 s 1 s
Reaction time after limit value is
exceeded 1/f_ist + 16 ms 1/f_ist + 16 ms
Waiting period with a monitored
start
With rising edge 30 ms 30 ms
With falling edge 30 ms 30 ms
Min. start pulse duration with a
monitored start
With rising edge 30 ms 30 ms
With falling edge 30 ms 30 ms
Supply interruption before de-ener-
gisation 20 ms 20 ms
Switch delay (selectable) 0 - 30 s 0 - 30 s
Delay on the select inputs (select-
able) 0 - 30 s 0 - 30 s
Start-up delay (selectable) 0 - 600 s 0 - 600 s
Environmental data 750330 751330
Climatic suitability EN 60068-2-78 EN 60068-2-78
Ambient temperature
Temperature range -20 - 55 °C -20 - 55 °C
Storage temperature
Temperature range -40 - 85 °C -40 - 85 °C