Datasheet
Relays for functional safety
Safety relays PNOZsigma
PNOZ s10
Pilz GmbH & Co. KG, Felix-Wankel-Straße 2, 73760 Ostfildern, Germany
Telephone: +49 711 3409-0, Telefax: +49 711 3409-133, E-Mail: info@pilz.com
2016-09
775
Relay outputs 750110 751110
Utilisation category of auxiliary con-
tacts
AC15 at 230 V 230 V
Max. current 2 A 2 A
DC13 (6 cycles/min) at 24 V 24 V
Max. current 2 A 2 A
Utilisation category in accordance
with UL
Voltage 240 V AC G. P. 240 V AC G. P.
With current 12 A 12 A
Voltage 24 V DC Resistive 24 V DC Resistive
With current 12 A 12 A
External contact fuse protection,
safety contacts
In accordance with the standard EN 60947-5-1 EN 60947-5-1
Max. melting integral 640 A²s 640 A²s
Blow-out fuse, quick 16 A 16 A
Blow-out fuse, slow 10 A 10 A
Blow-out fuse, gG 16 A 16 A
Circuit breaker 24V AC/DC,
characteristic B/C 10 A 10 A
External contact fuse protection,
auxiliary contacts
Max. melting integral 240 A²s 240 A²s
Blow-out fuse, quick 4 A 4 A
Blow-out fuse, slow 2 A 2 A
Blow-out fuse, gG 4 A 4 A
Circuit breaker 24 V AC/DC,
characteristic B/C 2 A 2 A
Contact material AgSnO2 + 0,2 µm Au AgSnO2 + 0,2 µm Au
Conventional thermal current
while loading several contacts
750110 751110
Ith per contact at UB DC;
AC1:240V,DC1:24V
Conv. therm. current with 1 con-
tact 12 A 12 A
Conv. therm. current with 2 con-
tacts 11 A 11 A
Conv. therm. current with 3 con-
tacts 9 A 9 A
Conv. therm. current with 4 con-
tacts 8 A 8 A