720
Expansion options
Please note the max. power consumption of the
contact expansion modules (see technical data
PNOZs7.1).
: Contact expansion module PNOZs7.1 with ter-
minator
: Contact expansion module PNOZs7.2
: Expansion module PNOZ s7, s8, s9, s10, s11 as
a terminator
: Base unit
: Contact expansion module PNOZs7.1
: Contact expansion module PNOZs7.2
: Contact expansion module PNOZs7.1
: Contact expansion module PNOZs7.2
: Contact expansion module PNOZs7.2 with ter-
minator
Wiring
Please note:
} Information given in the "Technical details [ 723]" must be followed.
} The output contacts 13-14, 23-24, 33-34 are safety contacts.
} To prevent contact welding, a fuse should be connected before the output contacts (see
Technical details [ 723]).
} Calculation of the max. cable length l
max
in the input circuit:
R
lmax
R
l
/ km
I
max
=
R
lmax
= max. overall cable resistance (see Technical details [ 723])
R
l
/km = cable resistance/km
} Use copper wire that can withstand 60/75°C.
} Sufficient fuse protection must be provided on all output contacts with capacitive and in-
ductive loads.