Datasheet

Relays for functional safety
Safety relays PNOZsigma
PNOZ s7
Pilz GmbH & Co. KG, Felix-Wankel-Straße 2, 73760 Ostfildern, Germany
Telephone: +49 711 3409-0, Telefax: +49 711 3409-133, E-Mail: info@pilz.com
2016-09
710
Relay outputs 750107 751107 751187
External contact fuse pro-
tection, safety contacts
In accordance with the
standard EN 60947-5-1 EN 60947-5-1 EN 60947-5-1
Max. melting integral 260 A²s 260 A²s 260 A²s
Blow-out fuse, quick 10 A 10 A 10 A
Blow-out fuse, slow 6 A 6 A 6 A
Blow-out fuse, gG 10 A 10 A 10 A
Circuit breaker 24V
AC/DC, characteristic
B/C 6 A 6 A 6 A
External contact fuse pro-
tection, auxiliary contacts
Max. melting integral 160 A²s 160 A²s 160 A²s
Blow-out fuse, quick 4 A 4 A 4 A
Blow-out fuse, slow 2 A 2 A 2 A
Blow-out fuse, gG 4 A 4 A 4 A
Circuit breaker 24 V
AC/DC, characteristic
B/C 2 A 2 A 2 A
Contact material AgCuNi + 0,2 µm Au AgCuNi + 0,2 µm Au AgCuNi + 0,2 µm Au
Conventional thermal
current while loading
several contacts
750107 751107 751187
Ith per contact at UB DC;
AC1:240V,DC1:24V
Conv. therm. current
with 1 contact 6 A 6 A 6 A
Conv. therm. current
with 2 contacts 5,5 A 5,5 A 5,5 A
Conv. therm. current
with 3 contacts 4,5 A 4,5 A 4,5 A
Conv. therm. current
with 4 contacts 4 A 4 A 4 A
Times 750107 751107 751187
Switch-on delay
With automatic start
after power on typ. 30 ms 30 ms 30 ms
With automatic start
after power on max. 50 ms 50 ms 50 ms