Datasheet

Relays for functional safety
Safety relays PNOZsigma
PNOZ s5
Pilz GmbH & Co. KG, Felix-Wankel-Straße 2, 73760 Ostfildern, Germany
Telephone: +49 711 3409-0, Telefax: +49 711 3409-133, E-Mail: info@pilz.com
2016-09
655
Times 750135 751135
Switch-on delay
With automatic start typ. 180 ms 180 ms
With automatic start max. 330 ms 330 ms
With automatic start after power
on typ. 1.430 ms 1.430 ms
With automatic start after power
on max. 1.900 ms 1.900 ms
With automatic start after power
on typ.
With automatic start after power
on max.
With manual start typ. 45 ms 45 ms
With manual start max. 85 ms 85 ms
With monitored start with rising
edge typ. 45 ms 45 ms
With monitored start with rising
edge max. 70 ms 70 ms
With monitored start with falling
edge typ. 60 ms 60 ms
With monitored start with falling
edge max. 80 ms 80 ms
Delay-on de-energisation
With E-STOP typ. 15 ms 15 ms
With E-STOP max. 20 ms 20 ms
With power failure typ. 75 ms 75 ms
With power failure max. 110 ms 110 ms
Recovery time at max. switching
frequency 1/s
After E-STOP 150 ms +tv 150 ms +tv
After power failure 200 ms 200 ms
Delay time tv 0,04 s, 0,1 s, 0,2 s, 0,3 s, 0,4 s,
0,5 s, 0,6 s, 0,7 s, 0,8 s, 1 s, 1,5 s,
2 s, 2,5 s, 3 s, 3,5 s, 4 s, 5 s, 6 s,
7 s, 8 s, 10 s, 12 s, 14 s, 15 s, 16
s, 20 s, 25 s, 30 s, 35 s, 40 s, 50
s, 60 s, 70 s, 80 s, 90 s, 100 s,
120 s, 140 s, 150 s, 160 s, 180 s,
200 s, 210 s, 240 s, 300 s
0,04 s, 0,1 s, 0,2 s, 0,3 s, 0,4 s,
0,5 s, 0,6 s, 0,7 s, 0,8 s, 1 s, 1,5 s,
2 s, 2,5 s, 3 s, 3,5 s, 4 s, 5 s, 6 s,
7 s, 8 s, 10 s, 12 s, 14 s, 15 s, 16
s, 20 s, 25 s, 30 s, 35 s, 40 s, 50
s, 60 s, 70 s, 80 s, 90 s, 100 s,
120 s, 140 s, 150 s, 160 s, 180 s,
200 s, 210 s, 240 s, 300 s
Time accuracy +/-1 % + +/-20 ms +/-1 % + +/-20 ms
Repetition accuracy +/-1 % + +/-20 ms +/-1 % + +/-20 ms
Repetition accuracy in the event of
an error +/-15 % + +/-20 ms +/-15 % + +/-20 ms
Max. delay time tv + 15 % + 20 ms tv + 15 % + 20 ms