Datasheet

Relays for functional safety
Safety relays PNOZ X
PNOZ X2.3P
Pilz GmbH & Co. KG, Felix-Wankel-Straße 2, 73760 Ostfildern, Germany
Telephone: +49 711 3409-0, Telefax: +49 711 3409-133, E-Mail: info@pilz.com
2016-09
62
Conventional thermal current
while loading several contacts
777304 787304
Ith per contact at UB AC;
AC1:240V,DC1:24V
Conv. therm. current with 1 con-
tact 6 A 6 A
Conv. therm. current with 2 con-
tacts 6 A 6 A
Conv. therm. current with 3 con-
tacts 5 A 5 A
Ith per contact at UB DC;
AC1:240V,DC1:24V
Conv. therm. current with 1 con-
tact 6 A 6 A
Conv. therm. current with 2 con-
tacts 6 A 6 A
Conv. therm. current with 3 con-
tacts 5 A 5 A
Times 777304 787304
Switch-on delay
With automatic start typ. 50 ms 50 ms
With automatic start max. 90 ms 90 ms
With automatic start after power
on typ. 60 ms 60 ms
With automatic start after power
on max. 100 ms 100 ms
With manual start typ. 40 ms 40 ms
With manual start max. 90 ms 90 ms
With monitored start typ. 40 ms 40 ms
With monitored start max. 70 ms 70 ms
Delay-on de-energisation
With E-STOP typ. 12 ms 12 ms
With E-STOP max. 30 ms 30 ms
With power failure typ. 60 ms 60 ms
With power failure max. 100 ms 100 ms
Recovery time at max. switching
frequency 1/s
After E-STOP 50 ms 50 ms
After power failure 150 ms 150 ms
Waiting period with a monitored
start 210 ms 210 ms
Min. start pulse duration with a
monitored start 40 ms 40 ms
Supply interruption before de-ener-
gisation 20 ms 20 ms