Datasheet
Relays for functional safety
Safety relays PNOZsigma
PNOZ s3
Pilz GmbH & Co. KG, Felix-Wankel-Straße 2, 73760 Ostfildern, Germany
Telephone: +49 711 3409-0, Telefax: +49 711 3409-133, E-Mail: info@pilz.com
2016-09
582
Relay outputs 750103 751103
Utilisation category
In accordance with the standard EN 60947-5-1 EN 60947-5-1
Utilisation category of safety con-
tacts
AC15 at 230 V 230 V
Max. current 5 A 5 A
DC13 (6 cycles/min) at 24 V 24 V
Max. current 5 A 5 A
Utilisation category in accordance
with UL
Voltage 240 V AC G.U. (same polarity) 240 V AC G.U. (same polarity)
With current 6 A 6 A
Voltage 24 V DC G. U. 24 V DC G. U.
With current 6 A 6 A
External contact fuse protection,
safety contacts
In accordance with the standard EN 60947-5-1 EN 60947-5-1
Max. melting integral 260 A²s 260 A²s
Blow-out fuse, quick 10 A 10 A
Blow-out fuse, slow 6 A 6 A
Blow-out fuse, gG 10 A 10 A
Circuit breaker 24V AC/DC,
characteristic B/C 6 A 6 A
Conventional thermal current 6 A 6 A
Contact material AgCuNi + 0,2 µm Au AgCuNi + 0,2 µm Au
Times 750103 751103
Switch-on delay
With automatic start typ. 170 ms 170 ms
With automatic start max. 300 ms 300 ms
With automatic start after power
on typ. 350 ms 350 ms
With automatic start after power
on max. 600 ms 600 ms
With manual start typ. 40 ms 40 ms
With monitored start with rising
edge typ. 35 ms 35 ms
With monitored start with rising
edge max. 50 ms 50 ms
With monitored start with falling
edge typ. 55 ms 55 ms
With monitored start with falling
edge max. 70 ms 70 ms