Datasheet

Relays for functional safety
Safety relays PNOZsigma
PNOZ s3
Pilz GmbH & Co. KG, Felix-Wankel-Straße 2, 73760 Ostfildern, Germany
Telephone: +49 711 3409-0, Telefax: +49 711 3409-133, E-Mail: info@pilz.com
2016-09
574
Block diagram/terminal configuration
Interface
expansion
module
Fig.: Centre: Front view with cover, right: Front view without cover
*Insulation between the non-marked area and the relay contacts: Basic insulation (over-
voltage category III), Protective separation (overvoltage category II)
Function description
}
In2+
Single-channel operation: no redundancy in the input circuit, earth faults in the start
circuit and input circuit are detected.
} Dual-channel operation without detection of shorts across contacts: Redundant input
circuit, detects PNOZ s3
earth faults in the start and input circuit,
short circuits in the input circuit and, with a monitored start, in the start circuit too.
}
In2-
Dual-channel operation with detection of shorts across contacts: Redundant input
circuit, detects PNOZ s3
earth faults in the start and input circuit,
Short circuits in the input circuit and, with a monitored start, in the start circuit too,
Shorts across contacts in the input circuit.
} Automatic start: Unit is active once the input circuit has been closed.
} Manual start Unit is active once the input circuit and the start circuit are closed.
} Monitored start with falling edge: Unit is active once
the input circuit is closed and then the start circuit is closed and opened again.
the start circuit is closed and then opened again once the input circuit is closed.