Datasheet
Relays for functional safety
Safety relays PNOZsigma
PNOZ s1
Pilz GmbH & Co. KG, Felix-Wankel-Straße 2, 73760 Ostfildern, Germany
Telephone: +49 711 3409-0, Telefax: +49 711 3409-133, E-Mail: info@pilz.com
2016-09
555
Relay outputs 750101 751101
Max. short circuit current IK 1 kA 1 kA
Utilisation category
In accordance with the standard EN 60947-4-1 EN 60947-4-1
Utilisation category of safety con-
tacts
AC1 at 240 V 240 V
Min. current 0,02 A 0,02 A
Max. current 3 A 3 A
Max. power 720 VA 720 VA
DC1 at 24 V 24 V
Min. current 0,02 A 0,02 A
Max. current 3 A 3 A
Max. power 72 W 72 W
Utilisation category
In accordance with the standard EN 60947-5-1 EN 60947-5-1
Utilisation category of safety con-
tacts
AC15 at 230 V 230 V
Max. current 1,5 A 1,5 A
DC13 (6 cycles/min) at 24 V 24 V
Max. current 1,5 A 1,5 A
Utilisation category in accordance
with UL
Voltage 240 V AC G. P. 240 V AC G. P.
With current 3 A 3 A
Voltage 24 V DC G. P. 24 V DC G. P.
With current 3 A 3 A
Pilot Duty B300, R300 B300, R300
External contact fuse protection,
safety contacts
In accordance with the standard EN 60947-5-1 EN 60947-5-1
Blow-out fuse, quick 4 A 4 A
Blow-out fuse, slow 2 A 2 A
Blow-out fuse, gG 4 A 4 A
Circuit breaker 24V AC/DC,
characteristic B/C 2 A 2 A
Conventional thermal current 3 A 3 A
Contact material AgSnO2 AgSnO2