Datasheet
Relays for functional safety
Safety relays PNOZ X
PNOZ X2.1VP
Pilz GmbH & Co. KG, Felix-Wankel-Straße 2, 73760 Ostfildern, Germany
Telephone: +49 711 3409-0, Telefax: +49 711 3409-133, E-Mail: info@pilz.com
2016-09
49
Relay outputs 777600 787600
Utilisation category
In accordance with the standard EN 60947-4-1 EN 60947-4-1
Utilisation category of safety con-
tacts delayed
AC1 at 240 V 240 V
Min. current 0,01 A 0,01 A
Max. current 6 A 6 A
Max. power 1500 VA 1500 VA
DC1 at 24 V 24 V
Min. current 0,01 A 0,01 A
Max. current 6 A 6 A
Max. power 150 W 150 W
Utilisation category
In accordance with the standard EN 60947-5-1 EN 60947-5-1
Utilisation category of safety con-
tacts delayed
AC15 at 230 V 230 V
Max. current 5 A 5 A
DC13 (6 cycles/min) at 24 V 24 V
Max. current 4 A 4 A
Utilisation category in accordance
with UL
Voltage 240 V AC G. P. 240 V AC G. P.
With current 6 A 6 A
Voltage 24 V DC Resistive 24 V DC Resistive
With current 6 A 6 A
Pilot Duty B300, R300 B300, R300
External contact fuse protection,
safety contacts
In accordance with the standard EN 60947-5-1 EN 60947-5-1
Max. melting integral 100 A²s 100 A²s
Blow-out fuse, quick 6 A 6 A
Blow-out fuse, slow 4 A 4 A
Blow-out fuse, gG 6 A 6 A
Circuit breaker 24V AC/DC,
characteristic B/C 4 A 4 A
Conventional thermal current 6 A 6 A
Contact material AgSnO2 + 0,2 µm Au AgSnO2 + 0,2 µm Au