Datasheet
Relays for functional safety
Safety relays PNOZ X
PZE 9P
Pilz GmbH & Co. KG, Felix-Wankel-Straße 2, 73760 Ostfildern, Germany
Telephone: +49 711 3409-0, Telefax: +49 711 3409-133, E-Mail: info@pilz.com
2016-09
489
Conventional thermal current
while loading several contacts
777140 787140
Ith per contact at UB AC;
AC1:240V,DC1:24V
Conv. therm. current with 1 con-
tact 8 A 8 A
Conv. therm. current with 2 con-
tacts 8 A 8 A
Conv. therm. current with 3 con-
tacts 8 A 8 A
Conv. therm. current with 4 con-
tacts 7,1 A 7,1 A
Conv. therm. current with 5 con-
tacts 6,3 A 6,3 A
Conv. therm. current with 6 con-
tacts 5,8 A 5,8 A
Conv. therm. current with 7 con-
tacts 5,4 A 5,4 A
Conv. therm. current with 8 con-
tacts 5 A 5 A
Ith per contact at UB DC;
AC1:240V,DC1:24V
Conv. therm. current with 1 con-
tact 8 A 8 A
Conv. therm. current with 2 con-
tacts 8 A 8 A
Conv. therm. current with 3 con-
tacts 8 A 8 A
Conv. therm. current with 4 con-
tacts 7,1 A 7,1 A
Conv. therm. current with 5 con-
tacts 6,3 A 6,3 A
Conv. therm. current with 6 con-
tacts 5,8 A 5,8 A
Conv. therm. current with 7 con-
tacts 5,4 A 5,4 A
Conv. therm. current with 8 con-
tacts 5 A 5 A
Times 777140 787140
Switch-on delay
With automatic start typ. 30 ms 30 ms
With automatic start max. 40 ms 40 ms
With automatic start after power
on typ. 30 ms 30 ms
With automatic start after power
on max. 40 ms 40 ms