Datasheet

Relays for functional safety
Safety relays PNOZ X
PZE X5P
Pilz GmbH & Co. KG, Felix-Wankel-Straße 2, 73760 Ostfildern, Germany
Telephone: +49 711 3409-0, Telefax: +49 711 3409-133, E-Mail: info@pilz.com
2016-09
477
Relay outputs 777150 787150
Utilisation category in accordance
with UL
Voltage 240 V AC G. P. 240 V AC G. P.
With current 8 A 8 A
Voltage 24 V DC G. P. Resistive 24 V DC G. P. Resistive
With current 5 A 5 A
Pilot Duty B300, R300 B300, R300
External contact fuse protection,
safety contacts
In accordance with the standard EN 60947-5-1 EN 60947-5-1
Max. melting integral 240 A²s 240 A²s
Blow-out fuse, quick 10 A 10 A
Blow-out fuse, slow 6 A 6 A
Blow-out fuse, gG 10 A 10 A
Circuit breaker 24V AC/DC,
characteristic B/C 6 A 6 A
Contact material AgSnO2 + 0,2 µm Au AgSnO2 + 0,2 µm Au
Conventional thermal current
while loading several contacts
777150 787150
Ith per contact at UB DC;
AC1:240V,DC1:24V
Conv. therm. current with 1 con-
tact 8 A 8 A
Conv. therm. current with 2 con-
tacts 8 A 8 A
Conv. therm. current with 3 con-
tacts 6,5 A 6,5 A
Conv. therm. current with 4 con-
tacts 5,6 A 5,6 A
Conv. therm. current with 5 con-
tacts 5 A 5 A
Times 777150 787150
Switch-on delay
With automatic start typ. 15 ms 15 ms
With automatic start max. 30 ms 30 ms
With automatic start after power
on typ. 15 ms 15 ms
With automatic start after power
on max. 30 ms 30 ms