Datasheet

Relays for functional safety
Safety relays PNOZ X
PNOZ XV3.1P
Pilz GmbH & Co. KG, Felix-Wankel-Straße 2, 73760 Ostfildern, Germany
Telephone: +49 711 3409-0, Telefax: +49 711 3409-133, E-Mail: info@pilz.com
2016-09
384
Times 777520 777522 777525
Switch-on delay
With automatic start
typ. 400 ms 400 ms 400 ms
With automatic start
max. 850 ms 850 ms 850 ms
With automatic start
after power on typ. 400 ms 400 ms 400 ms
With automatic start
after power on max. 870 ms 870 ms 870 ms
With monitored start
typ. 40 ms 40 ms 40 ms
With monitored start
max. 70 ms 70 ms 70 ms
Delay-on de-energisation
With E-STOP typ. 15 ms 15 ms 15 ms
With E-STOP max. 30 ms 30 ms 30 ms
With power failure typ. 110 ms 110 ms 110 ms
With power failure max. 150 ms 150 ms 150 ms
Recovery time at max.
switching frequency 1/s
After E-STOP 50 ms +tv 50 ms +tv 50 ms +tv
After power failure 200 ms 200 ms 200 ms
Delay time tv 0,1 s, 0,5 s, 1 s, 2 s, 4 s,
6 s, 8 s, 10 s, 15 s, 20 s,
25 s, 30 s
0,1 s, 0,2 s, 0,3 s, 0,4 s,
0,5 s, 0,6 s, 0,7 s, 0,8 s, 1
s, 1,5 s, 2 s, 3 s 3 s
Time accuracy -15 %/+15 % +50 ms -15 %/+15 % +50 ms -15 %/+15 % +50 ms
Repetition accuracy 2 % 2 % 2 %
Waiting period with a
monitored start 300 ms 300 ms 300 ms
Min. start pulse duration
with a monitored start 30 ms 30 ms 30 ms
Supply interruption before
de-energisation 20 ms 20 ms 20 ms
Simultaneity, channel 1
and 2 max.
Environmental data 777520 777522 777525
Climatic suitability EN 60068-2-78 EN 60068-2-78 EN 60068-2-78
Ambient temperature
Temperature range -10 - 55 °C -10 - 55 °C -10 - 55 °C
Storage temperature
Temperature range -40 - 85 °C -40 - 85 °C -40 - 85 °C
Climatic suitability
Humidity 93 % r. h. at 40 °C 93 % r. h. at 40 °C 93 % r. h. at 40 °C