Installation
} The unit should be installed in a control cabinet with a protection type of at least IP54.
} Use the notch on the rear of the unit to attach it to a DIN rail.
} Ensure the unit is mounted securely on a vertical DIN rail (35 mm) by using a fixing ele-
ment (e.g. retaining bracket or an end angle).
Wiring
Please note:
} Information given in the "Technical details [ 380]" must be followed.
} Delivery status of units with screw terminals: Link between S11-S12 (dual-channel input
circuit) and link between Y39-Y40 (reset circuit)
} Outputs 13-14, 23-24, 33-34 are instantaneous safety contacts, outputs 57-58, 67-68
are delay-on de-energisation safety contacts, output 41-42 is an instantaneous auxiliary
contact (e.g. for display).
} Auxiliary contact 41-42 shouldnot be used for safety circuits!
} Do not connect undesignated terminals.
} To prevent contact welding, a fuse should be connected before the output contacts (see
Technical details [ 380]).
} Calculation of the max. cable length l
max
in the input circuit:
R
lmax
R
l
/ km
I
max
=
R
lmax
= max. overall cable resistance (see Technical details [ 380])
R
l
/km = cable resistance/km
} Use copper wire that can withstand 60/75°C.
} Sufficient fuse protection must be provided on all output contacts with capacitive and in-
ductive loads.
} On units with U
B
24 – 240 VAC/DC: Connect operational earth terminal to functional
earth.
} Do not switch low currents using contacts that have been used previously with high cur-
rents.
} On 24 VDC devices:
The power supply must comply with the regulations for extra low voltages with protect-
ive electrical separation (SELV, PELV) in accordance with VDE 0100, Part 410.
} Ensure the wiring and EMC requirements of IEC 60204-1 are met.