Datasheet
Relays for functional safety
Safety relays PNOZ X
PNOZ XV3P
Pilz GmbH & Co. KG, Felix-Wankel-Straße 2, 73760 Ostfildern, Germany
Telephone: +49 711 3409-0, Telefax: +49 711 3409-133, E-Mail: info@pilz.com
2016-09
362
Times 777515 777517 777518
Min. start pulse duration
with a monitored start 30 ms 30 ms 30 ms
Supply interruption before
de-energisation 20 ms 20 ms 20 ms
Simultaneity, channel 1
and 2 max. ∞ ∞ ∞
Environmental data 777515 777517 777518
Climatic suitability EN 60068-2-78 EN 60068-2-78 EN 60068-2-78
Ambient temperature
Temperature range -10 - 55 °C -10 - 55 °C -10 - 55 °C
Storage temperature
Temperature range -40 - 85 °C -40 - 85 °C -40 - 85 °C
Climatic suitability
Humidity 93 % r. h. at 40 °C 93 % r. h. at 40 °C 93 % r. h. at 40 °C
Condensation during op-
eration Not permitted Not permitted Not permitted
EMC EN 60947-5-1, EN
61000-6-2, EN 61326-3-1
EN 60947-5-1, EN
61000-6-2, EN 61326-3-1
EN 60947-5-1, EN
61000-6-2, EN 61326-3-1
Vibration
In accordance with the
standard EN 60068-2-6 EN 60068-2-6 EN 60068-2-6
Frequency 10 - 55 Hz 10 - 55 Hz 10 - 55 Hz
Amplitude 0,35 mm 0,35 mm 0,35 mm
Airgap creepage
In accordance with the
standard EN 60947-1 EN 60947-1 EN 60947-1
Overvoltage category III / II III / II III / II
Pollution degree 2 2 2
Rated insulation voltage 250 V 250 V 250 V
Rated impulse withstand
voltage 4 kV 4 kV 4 kV
Protection type
Mounting area (e.g.
control cabinet) IP54 IP54 IP54
Housing IP40 IP40 IP40
Terminals IP20 IP20 IP20
Mechanical data 777515 777517 777518
Mounting position Any Any Any
Mechanical life 10,000,000 cycles 10,000,000 cycles 10,000,000 cycles