Datasheet
Relays for functional safety
Safety relays PNOZ X
PNOZ XV3P
Pilz GmbH & Co. KG, Felix-Wankel-Straße 2, 73760 Ostfildern, Germany
Telephone: +49 711 3409-0, Telefax: +49 711 3409-133, E-Mail: info@pilz.com
2016-09
361
Conventional thermal
current while loading
several contacts
777515 777517 777518
Ith per contact at UB DC;
AC1:240V,DC1:24V
Conv. therm. current
with 1 contact 8 A 8 A 8 A
Conv. therm. current
with 2 contacts 6,8 A 6,8 A 6,8 A
Conv. therm. current
with 3 contacts 5,5 A 5,5 A 5,5 A
Conv. therm. current
with 4 contacts 4,8 A 4,8 A 4,8 A
Conv. therm. current
with 5 contacts 4,3 A 4,3 A 4,3 A
Times 777515 777517 777518
Switch-on delay
With automatic start
typ. 350 ms 350 ms 350 ms
With automatic start
max. 650 ms 650 ms 650 ms
With automatic start
after power on typ. 385 ms 385 ms 385 ms
With automatic start
after power on max. 700 ms 700 ms 700 ms
With monitored start
typ. 35 ms 35 ms 35 ms
With monitored start
max. 70 ms 70 ms 70 ms
Delay-on de-energisation
With E-STOP typ. 15 ms 15 ms 15 ms
With E-STOP max. 30 ms 30 ms 30 ms
With power failure typ. 85 ms 85 ms 85 ms
With power failure max. 200 ms 200 ms 200 ms
Recovery time at max.
switching frequency 1/s
After E-STOP 50 ms +tv 50 ms +tv 50 ms +tv
After power failure 250 ms 250 ms 250 ms
Delay time tv
3 s 10 s
0,3 s, 5 s, 10 s, 20 s, 40
s, 60 s, 80 s, 100 s, 150
s, 200 s, 250 s, 300 s
Time accuracy -15 %/+15 % +50 ms -15 %/+15 % +50 ms -15 %/+15 % +50 ms
Repetition accuracy 2 % 2 % 2 %
Waiting period with a
monitored start 300 ms 300 ms 300 ms