Datasheet
Relays for functional safety
Safety relays PNOZ X
PNOZ XV2.1P
Pilz GmbH & Co. KG, Felix-Wankel-Straße 2, 73760 Ostfildern, Germany
Telephone: +49 711 3409-0, Telefax: +49 711 3409-133, E-Mail: info@pilz.com
2016-09
334
Relay outputs 777548 787540
External contact fuse protection,
delayed safety contacts
Max. melting integral 240 A²s 240 A²s
Blow-out fuse, quick 10 A 10 A
Blow-out fuse, slow 6 A 6 A
Blow-out fuse, gG 10 A 10 A
Circuit breaker 24 V AC/DC,
characteristic B/C 6 A 6 A
Contact material AgSnO2 + 0,2 µm Au AgSnO2 + 0,2 µm Au
Conventional thermal current
while loading several contacts
777548 787540
Ith per contact at UB AC;
AC1:240V,DC1:24V
Conv. therm. current with 1 con-
tact 8 A 8 A
Conv. therm. current with 2 con-
tacts 7 A 7 A
Conv. therm. current with 3 con-
tacts 5,7 A 5,7 A
Conv. therm. current with 4 con-
tacts 5 A 5 A
Ith per contact at UB DC;
AC1:240V,DC1:24V
Conv. therm. current with 1 con-
tact 8 A 8 A
Conv. therm. current with 2 con-
tacts 7 A 7 A
Conv. therm. current with 3 con-
tacts 5,7 A 5,7 A
Conv. therm. current with 4 con-
tacts 5 A 5 A
Times 777548 787540
Switch-on delay
With automatic start typ. 400 ms 400 ms
With automatic start max. 550 ms 550 ms
With automatic start after power
on typ. 820 ms 820 ms
With automatic start after power
on max. 1.100 ms 1.100 ms
With monitored start typ. 35 ms 35 ms
With monitored start max. 60 ms 60 ms