Service life graph
The service life graphs indicate the number of cycles from which failures due to wear must
be expected. The wear is mainly caused by the electrical load; the mechanical load is negli-
gible.
Service life graph: Safety contacts (N/O), instantaneous
Cycles x 1000
Switching current (A)
Example
} Inductive load: 0.2 A
} Utilisation category: AC15
} Contact service life: 1 000 000 cycles
Provided the application to be implemented requires fewer than 1 000 000 cycles, the PFH
value (see Technical details [ 279]) can be used in the calculation.
To increase the service life, sufficient spark suppression must be provided on all relay con-
tacts. With capacitive loads, any power surges that occur must be noted. With DC contact-
ors, use flywheel diodes for spark suppression.