Datasheet

Relays for functional safety
Safety relays PNOZ X
PNOZ X10.11P
Pilz GmbH & Co. KG, Felix-Wankel-Straße 2, 73760 Ostfildern, Germany
Telephone: +49 711 3409-0, Telefax: +49 711 3409-133, E-Mail: info@pilz.com
2016-09
241
Important for detection of shorts across contacts:
As this function for detecting shorts across contacts is not failsafe, it is tested by Pilz during
the final control check. If there is a danger of exceeding the cable runs, we recommend the
following test after the installation of the device:
1. Unit ready for operation (output contacts closed)
2. Short circuit the test terminals S12, S22 for detecting shorts across the inputs.
3. The unit's fuse must be triggered and the output contacts must open. Cable lengths in
the scale of the maximum length can delay the fuse triggering for up to 2 minutes.
4. Reset the fuse: remove the short circuit and switch off the supply voltage for approx. 1
minute.
Preparing for operation
Supply voltage AC DC
A1
A2
L+
L-
Input circuit Single-channel Dual-channel
E-STOP
without detection of shorts
across contacts
S1
Y3
S12
S12
S21
S11
S22
E-STOP
with detection of shorts across
contacts
Safety gate
without detection of shorts
across contacts
S1
Y3
S12
S12
S21
S11
S22