Datasheet

Relays for functional safety
Safety relays PNOZ X
PNOZ X10.11P
Pilz GmbH & Co. KG, Felix-Wankel-Straße 2, 73760 Ostfildern, Germany
Telephone: +49 711 3409-0, Telefax: +49 711 3409-133, E-Mail: info@pilz.com
2016-09
238
Block diagram/terminal configuration
Y1 Y2
A1 A2
S34S33
S22
Y3
S21
S12S11
S37
*Insulation between the non-marked area and the relay contacts: Basic insulation (over-
voltage category III), Protective separation (overvoltage category II)
Function Description
The safety relay PNOZ X10.11P provides a safety-oriented interruption of a safety circuit.
When supply voltage is supplied the "POWER" LED is lit. The unit is ready for operation
when the feedback loop Y1-Y2 and the start circuit S12-S34 are closed.
} Input circuit is closed (e.g. E-STOP pushbutton not operated):
LEDs "CH.1 IN", "CH.2IN" and "K3" go out.
LEDs "K1" and "K2" light as soon as relays K1 and K2 are in operating position.
LED "K3" goes out as soon as relay K3 is in rest position.
Safety contacts 13-14, 23-24, 33-34, 43-44, 53-54 and 63-64 are closed, auxiliary
contacts 71-72, 81-82, 91-92 and 01-02 are opened. The unit is active.
} Input circuit is opened (e.g. E-STOP pushbutton operated):
The LEDs "CH.1IN" and "CH.2 IN" go out.
LEDs "K1" and "K2" go out as soon as relays K1 and K2 are in rest position.
Safety contacts 13-14, 23-24, 33-34, 43-44, 53-54 and 63-64 are opened redund-
antly, auxiliary contacts 71-72, 81-82, 91-92 and 01-02 are closed.
Operating modes
} Single-channel operation: No redundancy in the input circuit, earth faults in the start
and input circuit are detected.
} Dual-channel operation with detection of shorts across contacts: Redundant input cir-
cuit, PNOZ X10.11P detects
earth faults in the start and input circuit,
short circuits in the input circuit,
shorts across contacts in the input circuit.