Installation
} The unit should be installed in a control cabinet with a protection type of at least IP54.
} Use the notch on the rear of the unit to attach it to a DIN rail.
} Ensure the unit is mounted securely on a vertical DIN rail (35 mm) by using a fixing ele-
ment (e.g. retaining bracket or an end angle).
Wiring
Please note:
} Information given in the "Technical details [ 222]" must be followed.
} Delivery status of units with screw terminals: Link between Y1-Y2 (feedback loop)
} Outputs 13-14, 23-24, 33-34, 43-44, 53-54, 63-64, 73-74 are safety contacts, the out-
puts 81-82, 91-92 are auxiliary contacts (e.g. for display).
} Do notuse auxiliary contacts 81-82, 91-92 and semiconductor outputs Y32, Y35 for
safety circuits!
} Do not connect undesignated terminals.
} To prevent contact welding, a fuse should be connected before the output contacts (see
Technical details [ 222]).
} Calculation of the max. cable length l
max
in the input circuit:
R
lmax
R
l
/ km
I
max
=
R
lmax
= max. overall cable resistance (see Technical details [ 222])
R
l
/km = cable resistance/km
} Use copper wire that can withstand 60/75°C.
} Sufficient fuse protection must be provided on all output contacts with capacitive and in-
ductive loads.
} Do not switch low currents using contacts that have been used previously with high cur-
rents.
} When connecting magnetically operated, reed proximity switches, ensure that the max.
peak inrush current (on the input circuit) does not overload the proximity switch.
} 777607, 777609, 787609 units or 777606, 787606 units, when the supply voltage is
connected via B1 and B2:
The power supply must comply with the regulations for extra low voltages with safe
electrical separation (SELV, PELV) in accordance with VDE 0100, part 410.
} Ensure the wiring and EMC requirements of IEC 60204-1 are met.