Function Description
The safety relay PNOZ X9P provides a safety-oriented interruption of a safety circuit. When
supply voltage is supplied the "POWER" LED is lit. The unit is ready for operation when the
feedback loop Y1-Y2 and the start circuit S33-S34 are closed. The "START" LED is lit.
} Input circuit is closed (e.g. E-STOP pushbutton not operated):
The LEDs "CH.1IN" and "CH.2 IN" are lit.
Safety contacts 13-14, 23-24, 33-34, 43-44, 53-54, 63-64 and 73-74 are closed, the
auxiliary contacts 81-82 and 91-92 are opened. The unit is active.
A high signal is present at the semiconductor output switch state Y32.
The LEDs "CH.1 OUT" and "CH.2 OUT" are lit. The "START" LED goes out.
} Input circuit is opened (e.g. E-STOP pushbutton operated):
The LEDs "CH.1IN" and "CH.2 IN" go out.
Safety contacts 13-14, 23-24, 33-34, 43-44, 53-54, 63-64 and 73-74 are opened re-
dundantly, the auxiliary contacts 81-82 and 91-92 are closed.
A low signal is present at the semiconductor output switch state Y32.
The LEDs "CH.1 OUT" and "CH.2 OUT" go out.
} A high signal is present at semi-conductor output Y35 if the supply voltage is present
and the internal fuse has not blown.
Operating modes
} Single-channel operation: No redundancy in the input circuit, earth faults in the start
and input circuit are detected.
} Dual-channel operation without detection of shorts across contacts: Redundant input
circuit, detects PNOZ X9P
earth faults in the start and input circuit,
short circuits in the input circuit.
} Dual-channel operation with detection of shorts across contacts: Redundant input cir-
cuit, PNOZ X9P detects
earth faults in the start and input circuit,
short circuits in the input circuit,
shorts across contacts in the input circuit.
} Automatic start: Unit is active once the input circuit has been closed.
} Manual start: Unit is active once the input circuit and the start circuit are closed.
} Monitored start: Unit is active once
the input circuit is closed and then the start circuit is closed and opened again.
the start circuit is closed and then opened again once the input circuit is closed.