Datasheet
Relays for functional safety
Safety relays PNOZ X
PNOZ X8P
Pilz GmbH & Co. KG, Felix-Wankel-Straße 2, 73760 Ostfildern, Germany
Telephone: +49 711 3409-0, Telefax: +49 711 3409-133, E-Mail: info@pilz.com
2016-09
204
Times 787760 787764 787766
Switch-on delay
With automatic start
typ. 160 ms 175 ms 175 ms
With automatic start
max. 200 ms 220 ms 220 ms
With automatic start
after power on typ. 185 ms 200 ms 200 ms
With automatic start
after power on max. 220 ms 250 ms 250 ms
With manual start typ. 190 ms 190 ms 190 ms
With manual start max. 250 ms 250 ms 250 ms
With monitored start
typ. 130 ms 130 ms 130 ms
With monitored start
max. 180 ms 180 ms 180 ms
Delay-on de-energisation
With E-STOP typ. 15 ms 15 ms 15 ms
With E-STOP max. 30 ms 30 ms 30 ms
With power failure typ. 100 ms 160 ms 160 ms
With power failure max. 200 ms 220 ms 220 ms
Recovery time at max.
switching frequency 1/s
After E-STOP 50 ms 50 ms 50 ms
After power failure 180 ms 250 ms 250 ms
Min. start pulse duration
with a monitored start 30 ms 30 ms 30 ms
Supply interruption before
de-energisation 35 ms 35 ms 35 ms
Environmental data 787760 787764 787766
Climatic suitability EN 60068-2-78 EN 60068-2-78 EN 60068-2-78
Ambient temperature
Temperature range -10 - 55 °C -10 - 55 °C -10 - 55 °C
Storage temperature
Temperature range -40 - 85 °C -40 - 85 °C -40 - 85 °C
Climatic suitability
Humidity 93 % r. h. at 40 °C 93 % r. h. at 40 °C 93 % r. h. at 40 °C
Condensation during op-
eration Not permitted Not permitted Not permitted
EMC EN 60947-5-1, EN
61000-6-2, EN 61326-3-1
EN 60947-5-1, EN
61000-6-2, EN 61326-3-1
EN 60947-5-1, EN
61000-6-2, EN 61326-3-1