Datasheet
Relays for functional safety
Safety relays PNOZ X
PNOZ X1P
Pilz GmbH & Co. KG, Felix-Wankel-Straße 2, 73760 Ostfildern, Germany
Telephone: +49 711 3409-0, Telefax: +49 711 3409-133, E-Mail: info@pilz.com
2016-09
19
Relay outputs 777100 787100
External contact fuse protection,
safety contacts
In accordance with the standard EN 60947-5-1 EN 60947-5-1
Max. melting integral 100 A²s 100 A²s
Blow-out fuse, quick 6 A 6 A
Blow-out fuse, slow 4 A 4 A
Blow-out fuse, gG 6 A 6 A
Circuit breaker 24V AC/DC,
characteristic B/C 4 A 4 A
External contact fuse protection,
auxiliary contacts
Max. melting integral 100 A²s 100 A²s
Blow-out fuse, quick 6 A 6 A
Blow-out fuse, slow 4 A 4 A
Blow-out fuse, gG 6 A 6 A
Circuit breaker 24 V AC/DC,
characteristic B/C 4 A 4 A
Contact material AgSnO2 + 0,2 µm Au AgSnO2 + 0,2 µm Au
Conventional thermal current
while loading several contacts
777100 787100
Ith per contact at UB DC;
AC1:240V,DC1:24V
Conv. therm. current with 1 con-
tact 6 A 6 A
Conv. therm. current with 2 con-
tacts 6 A 6 A
Conv. therm. current with 3 con-
tacts 4,5 A 4,5 A
Times 777100 787100
Switch-on delay
With automatic start typ. 60 ms 60 ms
With automatic start max. 120 ms 120 ms
With manual start typ. 50 ms 50 ms
With manual start max. 120 ms 120 ms
Delay-on de-energisation
With E-STOP typ. 55 ms 55 ms
With E-STOP max. 90 ms 90 ms
With power failure typ. 55 ms 55 ms
With power failure max. 90 ms 90 ms
Recovery time at max. switching
frequency 1/s
After E-STOP 150 ms 150 ms
After power failure 150 ms 150 ms