Datasheet
Relays for functional safety
Safety relays PNOZ X
PNOZ X7P
Pilz GmbH & Co. KG, Felix-Wankel-Straße 2, 73760 Ostfildern, Germany
Telephone: +49 711 3409-0, Telefax: +49 711 3409-133, E-Mail: info@pilz.com
2016-09
170
Relay outputs 777053 777056 777059
Utilisation category of
safety contacts
AC15 at 230 V 230 V 230 V
Max. current 4 A 4 A 5 A
DC13 (6 cycles/min) at 24 V 24 V 24 V
Max. current 4 A 4 A 6 A
Utilisation category in ac-
cordance with UL
Voltage 240 V AC G. P. 240 V AC G. P. 240 V AC G. P.
With current 4 A 4 A 6 A
Voltage 24 V DC Resistive 24 V DC Resistive 24 V DC Resistive
With current 4 A 4 A 6 A
Pilot Duty C300, R300 C300, R300 C300, R300
External contact fuse pro-
tection, safety contacts
In accordance with the
standard EN 60947-5-1 EN 60947-5-1 EN 60947-5-1
Max. melting integral 240 A²s 240 A²s 240 A²s
Blow-out fuse, quick 4 A 4 A 6 A
Blow-out fuse, slow 4 A 4 A 4 A
Blow-out fuse, gG 4 A 4 A 6 A
Circuit breaker 24V
AC/DC, characteristic
B/C 4 A 4 A 4 A
Conventional thermal cur-
rent – – 6 A
Contact material AgSnO2 + 0,2 µm Au AgSnO2 + 0,2 µm Au AgSnO2 + 0,2 µm Au
Conventional thermal
current while loading
several contacts
777053 777056 777059
Ith per contact at UB AC;
AC1:240V,DC1:24V
Conv. therm. current
with 1 contact 4 A 4 A –
Conv. therm. current
with 2 contacts 3 A 3 A –