Datasheet

Relays for functional safety
Safety relays PNOZ X
PNOZ X3P
Pilz GmbH & Co. KG, Felix-Wankel-Straße 2, 73760 Ostfildern, Germany
Telephone: +49 711 3409-0, Telefax: +49 711 3409-133, E-Mail: info@pilz.com
2016-09
137
Times 777310 777313
Switch-on delay
With automatic start typ. 250 ms 330 ms
With automatic start max. 500 ms 450 ms
With automatic start after power
on typ. 280 ms 750 ms
With automatic start after power
on max. 550 ms 1.000 ms
With monitored start typ. 35 ms 35 ms
With monitored start max. 50 ms 50 ms
Delay-on de-energisation
With E-STOP typ. 15 ms 25 ms
With E-STOP max. 30 ms 30 ms
With power failure typ. 50 ms
With power failure max. 70 ms
With power failure typ. UB 240 V 1500 ms
With power failure max. UB 240
V 2200 ms
With power failure typ. UB 24 V 150 ms
With power failure max. UB 24 V 180 ms
Recovery time at max. switching
frequency 1/s
After E-STOP 50 ms 50 ms
After power failure 100 ms 200 ms
After power failure on wide-
range power supply 2250 ms
Waiting period with a monitored
start 300 ms 200 ms
Min. start pulse duration with a
monitored start 30 ms 30 ms
Supply interruption before de-ener-
gisation 20 ms 20 ms
Simultaneity, channel 1 and 2 max.
Environmental data 777310 777313
Climatic suitability EN 60068-2-78 EN 60068-2-78
Ambient temperature
Temperature range -20 - 55 °C -20 - 55 °C
Storage temperature
Temperature range -40 - 85 °C -40 - 85 °C
Climatic suitability
Humidity 93 % r. h. at 40 °C 93 % r. h. at 40 °C
Condensation during operation Not permitted Not permitted
EMC EN 60947-5-1, EN 61000-6-2, EN
61326-3-1
EN 60947-5-1, EN 61000-6-2, EN
61000-6-3, EN 61326-3-1