Datasheet
Relays for functional safety
Safety relays PNOZ X
PNOZ X2.9P
Pilz GmbH & Co. KG, Felix-Wankel-Straße 2, 73760 Ostfildern, Germany
Telephone: +49 711 3409-0, Telefax: +49 711 3409-133, E-Mail: info@pilz.com
2016-09
123
Mechanical data 777300 787300
Spring-loaded terminals: Terminal
points per connection – 2
Stripping length with spring-loaded
terminals – 8 mm
Dimensions
Height 94 mm 101 mm
Width 22,5 mm 22,5 mm
Depth 121 mm 121 mm
Weight 180 g 180 g
Where standards are undated, the 2014-07 latest editions shall apply.
Safety characteristic data
Operating
Mode
EN ISO
13849-1:
2015
PL
EN ISO
13849-1:
2015
Category
EN 62061
SIL CL
EN 62061
PFH
D
[1/h]
IEC 61511
SIL
IEC 61511
PFD
EN ISO
13849-1:
2015
T
M
[year]
– PL e Cat. 4 SIL CL 3 2,31E-09 SIL 3 2,03E-06 20
All the units used within a safety function must be considered when calculating the safety
characteristic data.
Supplementary data
The PFH value depends on the switching frequency and the load on the relay output.
If the service life graphs are not accessible, the stated PFH value can be used irrespective
of the switching frequency and the load, as the PFH value already considers the relay's
B10d value as well as the failure rates of the other components.
Service life graph
The service life graphs indicate the number of cycles from which failures due to wear must
be expected. The wear is mainly caused by the electrical load; the mechanical load is negli-
gible.