Conventional thermal current
while loading several contacts
777300 787300
Ith per contact at UB DC;
AC1:240V,DC1:24V
Conv. therm. current with 1 con-
tact 6 A 6 A
Conv. therm. current with 2 con-
tacts 6 A 6 A
Conv. therm. current with 3 con-
tacts 4,5 A 4,5 A
Times 777300 787300
Switch-on delay
With automatic start typ. 200 ms 200 ms
With automatic start max. 400 ms 400 ms
With automatic start after power
on typ. 200 ms 200 ms
With automatic start after power
on max. 400 ms 400 ms
With manual start typ. 100 ms 100 ms
With manual start max. 400 ms 400 ms
With monitored start typ. 30 ms 30 ms
With monitored start max. 50 ms 50 ms
Delay-on de-energisation
With E-STOP typ. 10 ms 10 ms
With E-STOP max. 20 ms 20 ms
With power failure typ. 70 ms 70 ms
With power failure max. 120 ms 120 ms
Recovery time at max. switching
frequency 1/s
After E-STOP 50 ms 50 ms
After power failure 150 ms 150 ms
Waiting period with a monitored
start 200 ms 200 ms
Min. start pulse duration with a
monitored start 30 ms 30 ms
Supply interruption before de-ener-
gisation 20 ms 20 ms
Simultaneity, channel 1 and 2 max. ∞ ∞
Environmental data 777300 787300
Climatic suitability EN 60068-2-78 EN 60068-2-78
Ambient temperature
Temperature range -10 - 55 °C -10 - 55 °C
Storage temperature
Temperature range -40 - 85 °C -40 - 85 °C