OperatingManualBAPSENsl1.0p1.1/1.1VA/2.1/2.2
21909EN09
9
Functiondescription
U
B
A1 A2
S31
12
22
Power supply
Power/Fault
&
&
Safety Gate
Lock
Receiver
Magnet
Actuator
Input
S21
S11
&
Y32
Thereisahighsignalatsafetyoutputs12and22ifthefollowingoccursimultaneously:
} Theactuatoriswithintheresponserange(safetygateclosed)and
} InputsS11andS21arehighand
} InputS31ishigh(controlcommandformagneticguardlocking)and
} Theholdingforceofthelockingmagnethasbeentestedsuccessfully.
Safetyoutputs12and22arelowifatleastoneofthefollowingconditionsaremet:
} Theactuatorisoutsidetheresponserangeor
} InputsS11orS21arelowor
} InputS31(controlcommandformagneticguardlocking)islowor
} Theholdingforceofthelockingmagnethasnotbeentestedsuccessfully.
SignaloutputY32
ThesignaloutputY32receivesahighsignaliftheactuatoriswithintheresponserange
(safetygateclosed).
FeasibilitymonitoringforsafetyinputsS11andS21
} Ifonesafetyinputswitchesfromhightolow,whiletheothersafetyinputremainshigh,
anunequalstatusisdisplayed.
} Ifthissafetyinputswitchesbackfromlowtohigh,whiletheothersafetyinputremains
high,afeasibilityerrorisdisplayedandapartialoperationlockistriggered.TheOSSDs
areswitchedoffduringthepartialoperationlock.