Datasheet
BAPSENsl1.0p1.1/1.1VA/2.1/2.2
OperatingManualBAPSENsl1.0p1.1/1.1VA/2.1/2.2
21909EN09
11
Guidelinesforcablelength
Themax.cablelengthdependsonthevoltagedropatthesensorcables.Thelevelof
voltagedropisdeterminedbythe:
} Cableresistance
} Currentofthedeviceandthecurrentloadofthesafetyoutputs12and22
Ifthelevelofthesupplyvoltageatthedeviceconnectorfallsbelowtheminimumpermitted
value(seeTechnicaldetails:Systemwithnormalactuator[ 25],Systemwithfreemov
ingactuator[ 28],underelectricaldata),theelectromagnetisnolongeractivatedreli
ably.The"Lock"LEDregistersanerrorwhenguardlocking.
Possibleremedies:
} Setthesupplyvoltageconstantlytotheuppertolerancerange(seeTechnicaldetails:
Systemwithnormalactuator[ 25],Systemwithfreemovingactuator[ 28],un
derelectricaldata)
} Selectahighercablecrosssection
} Reducetheloadonthesafetyoutput,e.g.withanelectricalevaluationdevice(PNOZ
e1.1p,5mA/channel)
Recommendedcablecrosssections
Prerequisite:
} Supplyvoltage:24V
} Cabletype:LiYY8x0.25mm²(79Ohm/km)fromPilz
Max.loadpersafetyoutput 100mA 500mA
Cablelength 45m 24m
Ifcablelengthsgreaterthanthosestatedinthetablearerequired,pleasecontactPilz.
Pinassignment
8pinM12connector
PIN Function Terminaldesignation
Cablecolour(Pilz
cable)
1 Input,channel2 S21 White
2 +24UB A1 Brown
3 Output,channel1 12 Green
4 Output,channel2 22 Yellow
5 Signaloutput"Lock" Y32 Grey
6 Input,channel1 S11 Pink
7 0VUB A2 Blue
8 "Lock_Unlock" S31 Red