Technical data

TRIO-PS/1AC/24DC/5
102777_02_en PHOENIX CONTACT 5
Conformance with EMC directive 89/336/EEC
Immunity to interference in acc. with EN 61000-6-2
Discharge of static electricity
Housing Level 3
Contact discharge 6 kV
Discharge in air 8 kV
Comments Criterion B
Electromagnetic HF field
Housing Level 3
Frequency range 80 MHz ... 3 GHz
Field intensity 10 V/m
Comments Criterion A
Fast transients (burst)
Input 4 kV (level 4 - asymmetrical: conductor to ground)
Output 2 kV (level 3 - asymmetrical: conductor to ground)
Comments Criterion A
Surge current loads (Surge)
Input/Output 4 kV (level 4 - asymmetrical: conductor to ground)
2 kV (level 4 - symmetrical: conductor to conductor)
Comments Criterion A
Conducted interference
Input/output Level 3 - asymmetrical
Frequency range 0.1 MHz ... 80 MHz
Voltage 10 V
Comments Criterion A
Voltage dips
Input (mains buffering > 10 ms)
Comments Criterion B
Emitted interference in acc. with EN 61000-6-3
Radio interference voltage in acc. with EN 55011 EN 55011 (EN 55022) Class B, area of application: Industry and residential
Emitted radio interference in acc. with EN 55011 EN 55011 (EN 55022) Class B, area of application: Industry and residential