Technical data

TRIO-PS/1AC/24DC/5
102777_02_en PHOENIX CONTACT 3
Description Type Order No. Pcs./Pkt.
Primary switched power supply, 1-phase, output current: 5 A TRIO-PS/1AC/24DC/5 2866310 1
Input data
Input nominal voltage range 100 V AC ... 240 V AC
AC input voltage range 85 V AC ... 264 V AC (derating < 90 V AC: 2.5% per Kelvin)
AC frequency range 45 Hz ... 65 Hz
Current consumption 1.65 A (120 V AC)
0.9 A (230 V AC)
Inrush current limitation < 15 A
I
2
t 1.1 A
2
s
Power failure bypass > 20 ms (120 V AC)
> 110 ms (230 V AC)
Typical response time < 1 s
Power factor (cos phi) 0.72
Protective circuitry Transient surge protection Varistor
Input fuse, integrated 3.15 A (slow-blow, internal)
Recommended backup fuse for mains protection 6 A
10 A
16 A (characteristic B)
Discharge current to PE < 3.5 mA
Output data
Nominal output voltage 24 V DC ±1%
Setting range of the output voltage 22.5 V DC ... 29.5 V DC
Output current 5 A (0°C ... 55°C)
Derating Above +55°C: 2.5% per Kelvin
Current limitation Approx. 10 A (for short circuit)
Max. capacitive load Unlimited
Control deviation < 1 % (change in load, static 10% ... 90%)
< 2 % (change in load, dynamic 10% ... 90%)
< 0.1 % (change in input voltage ±10%)
Power loss nominal load max. 18 W
Maximum power dissipation idling 1.1 W
Efficiency > 89 %
Ascent time < 2 ms (U
OUT
(10% ... 90%))
Residual ripple < 20 mV
PP
Peak switching voltages < 30 mV
PP
Connection in parallel Yes, for redundancy and increased capacity
Connection in series No
Surge protection against internal surge voltages Yes, < 35 V DC
Resistance to reverse feed 35 V DC
Signal output DC OK active
Status display "DC OK" LED green / U
OUT
> 21.5 V: LED lights up
Order data
Technical data