Technical data
TRIO-PS/1AC/24DC/5
102777_02_en PHOENIX CONTACT 12
I [A]
OUT
U [V]
OUT
U
N
I
N
Function
Output characteristic curve
The device functions following the U/I characteristic curve.
Under load, the working point follows this curve. The output
current is limited in the event of a short circuit or overload.
Thereby, the device does not switch off, but rather supplies
a continuous output current.
The secondary voltage is reduced until the short circuit or
overload on the secondary side has been remedied. The U/I
characteristic curve ensures that both heavily capacitive
loads and loads with DC/DC converters in the primary circuit
can be supplied. Downstream fuses are triggered. Selectivity
in the design of your system is guaranteed at all times.
U
N
= 24 V
I
N
= 5 A
P
N
= 120 W
0
0
I
N
20 40 60
Ambient temperature [°C]
Output current [A]
Thermal behavior
With an ambient temperature of up to +55°C, the device sup-
plies the continuous output current of I
N
. In the case of ambi-
ent temperatures above +55°C, the output current must be
reduced by 2.5% per Kelvin increase in temperature. The de-
vice does not switch off at ambient temperatures of +70°C or
thermal overload. The output capacity is reduced as far as
necessary to provide device protection. After it has cooled
down, the output capacity is increased again.