User manual
FL SWITCH MM HS
3-28
PHOENIX CONTACT 6874_en_09
3.2.10 FL IF 2POF SCRJ-D
3.2.10.1 Default Upon Delivery
When the interface modules are inserted, they are preset with a data transmission rate of
100 Mbps and full duplex mode, and link monitoring is not activated for the fiber optic ports.
3.2.10.2 Functions
– Line monitoring
According to standard IEEE 802.3, the switch monitors the connected fiber optic
cables for interrupts.
– Far End Fault Detection indicates that the connection in the direction of the partner is
not OK (the partner does not indicate a link) and therefore at least one fiber within the
fiber optic cable is faulty or has not been assembled correctly.
Hot plugging
When inserting and removing interface modules, you do not have to switch off the supply
voltage. The interface modules are detected automatically and logged to the network
management.
If the FL IF 2POF SCRJ ... interface is removed and another interface type is inserted in
its place, the ports are set to auto negotiation.
If a fiber optic interface module is inserted in an MMS that has already been
parameterized, the existing configuration remains active.
– The data transmission rate is set to 100 Mbps
– The duplex method is set to full duplex
If the module is removed, auto negotiation is enabled.
Ports that are not being used are considered cable interrupts. In addition, a fiber optic
path to a deactivated termination device is also considered a cable interrupt, as the
connected device cannot send a link test pulse because it is switched off.