User manual
Configuration and Diagnostics
6874_en_09 PHOENIX CONTACT 4-89
flWorkFWInfoDisplay
flWorkFWCtrl
OID 1.3.6.1.4.1.4346.11.11.11.2
flWorkFWCtrlBasic
OID 1.3.6.1.4.1.4346.11.11.11.2.1
flWorkFWCtrlReset
flWorkFWCtrlHttp
flWorkFWCtrlTelnet
Syntax Display string
Access Read
Description Contains additional information/error states for the firmware.
OID 1.3.6.1.4.1.4346.11.11.11.1.13
Syntax Display string
Access Read
Description Contains the current data from the diagnostic display.
OID 1.3.6.1.4.1.4346.11.11.11.2.1.1
Syntax Integer
Access Read and write
Description With write access, a reset can be executed with "2".
With read access, the value is always "1". When a reset is triggered, "rb" is indicated in
the display.
OID 1.3.6.1.4.1.4346.11.11.11.2.1.6
Syntax Integer
Access Read and write
Description This object can be used to disable the web server for the switch. The modification only
takes effect after a restart:
Web server enabled 2
Web server disabled 1
OID 1.3.6.1.4.1.4346.11.11.11.2.1.7
Syntax Integer
Access Read and write
Description This object can be used to disable the Telnet function for the MMS. The modification only
takes effect after a restart:
Telnet activated 2
Telnet deactivated 1