Datasheet

https://www.phoenixcontact.com/us/produkte/2938976
Nov 10, 20132/7
Power supply unit-QUINT-PS-100-240AC/48DC/20-2938976
Technical data
Input data
Input voltage range AC
85 V AC ... 264 V AC
Input voltage range DC
90 V DC ... 350 V DC
AC frequency range
45 Hz ... 65 Hz
Frequency range DC
0 Hz
Current consumption
approx. 11 A (120 V AC)
Current consumption
4.5 A (230 V AC)
Nominal power consumption
960 W
Inrush surge current
< 15 A (typical)
Power failure bypass
> 20 ms (120 V AC)
Power failure bypass
> 20 ms (230 V AC)
Input fuse
20 A (fast blow, internal)
Type of protection
Transient surge protection
Protective circuit/component
Varistor
Output data
Nominal output voltage
48 V DC ±1%
Setting range of the output voltage
30 V DC ... 56 V DC (> 48 V constant capacity)
Output current
20 A (-25 °C ... 60 °C)
Output current
22.5 A (with POWER BOOST, < 40°C permanent)
Derating
60 °C ... 70 °C (2.5%/K)
Connection in parallel
Yes, for redundancy and increased capacity
Connection in series
Yes
Max. capacitive load
Unlimited
Current limitation
Approx. I
BOOST
= 22.5 A (for short-circuit)
Control deviation
< 1 % (change in load, static 10% ... 90%)
Control deviation
< 2 % (change in load, dynamic 10% ... 90%)
Control deviation
< 0.1 % (change in input voltage ±10%)
Residual ripple
< 25 mV
PP
(with nominal values)
Peak switching voltages nominal load
< 30 mV
PP
(20 MHz)
Maximum power dissipation NO-Load
28 W
Power loss nominal load max.
80 W
General
Net weight
3.5 kg
Operating voltage display
Green LED
Efficiency
> 92 % (for 230 V AC and nominal values)
Insulation voltage input/output
4 kV AC (type test)
Insulation voltage input/output
2 kV AC (routine test)
Protection class
I, with PE connection
MTBF (IEC 61709, SN 29500)
> 500000 h
Mounting position
horizontal DIN rail NS 35, EN 60715
Assembly instructions
Can be aligned: Horizontally 0 mm, vertically 50 mm