Datasheet

https://www.phoenixcontact.com/us/produkte/2938837
Nov 14, 20132/6
Power supply unit-MINI-PS-100-240AC/24DC/4-2938837
Technical data
Input data
Nominal input voltage range
100 V AC ... 240 V AC
Input voltage range AC
85 V AC ... 264 V AC
Input voltage range DC
90 V DC ... 350 V DC
AC frequency range
45 Hz ... 65 Hz
Current consumption
1.3 A (120 V AC)
Current consumption
0.8 A (230 V AC)
Current consumption
1.3 A (90 V DC)
Current consumption
0.4 A (350 V DC)
Inrush surge current
< 15 A (typical)
Power failure bypass
> 20 ms (120 V AC)
Power failure bypass
> 100 ms (230 V AC)
Input fuse
3.15 A (slow-blow, internal)
Type of protection
Transient surge protection
Protective circuit/component
Varistor
Output data
Nominal output voltage
24 V DC ±1%
Setting range of the output voltage
22.5 V DC ... 28.5 V DC (> 24 V constant capacity)
Output current
4 A (-25 °C ... 60 °C)
Output current
5 A (with POWER BOOST, -25°C ... 40°C permanent)
Derating
60 °C ... 70 °C (2.5%/K)
Connection in parallel
Yes, for redundancy and increased capacity
Connection in series
Yes
Starting delay with capacitive load
(Unrestricted)
Max. capacitive load
Unlimited
Current limitation
Approx 9 A (in the event of a short-circuit)
Control deviation
(change in load, static 10% ... 90%)
Control deviation
< 3 % (change in load, dynamic 10% ... 90%)
Control deviation
< 0.1 % (change in input voltage ±10%)
Residual ripple
< 20 mV
PP
(20 MHz)
Peak switching voltages nominal load
< 100 mV
PP
(20 MHz)
Maximum power dissipation NO-Load
2.5 W
Power loss nominal load max.
12 W
General
Net weight
0.4 kg
Operating voltage display
Green LED
Efficiency
> 88 % (for 230 V AC and nominal values)
Insulation voltage input/output
3 kV (type test)
Insulation voltage input/output
3 kV (Routine test)
Protection class
II (in an enclosed control cabinet)
MTBF (IEC 61709, SN 29500)
> 815000 h (According to EN 29500)