Datasheet

PHOENIX CONTACT page 6 of 8
Power Supply, Primary Switch Mode, Narrow Design – MINI-PS-100-240AC/24DC/4
+
LN
L
N
PE
MINI
+
LN
L
PEN
MINI
+
LN
L
N
MINI
+–
MINI
L1
L2
L3
N
PE
L N
+–
MINI
L1
L2
L3
PEN
L N
+–
MINI
L1
L2
L3
N
L N
L1
L2
L3
PE
+
L
N
MINI
TN-S network TN-C network TT network
6.2. Connection of Various Types of Network: 100 - 240 V AC Networks
Figure 08
IT network
L(+) N(-)
MINI-PS-100-240
AC
Order No.: 29 38
8
3
Power Supply
INPUT
OUTPUT
AC:
100-240V
50-60Hz
Range:
85-264V
1.6-0.7A
DC:
90-350V
1.3-0.4A
24V DC
±1%
4A
MINI POWER
DC
OK
OUT DC 24V 4 A
22.5-28.5
V DC
L(+)
N(-)
IN AC 100-240 V
+
+
DC
OK
22
22
44
44
11
11
33
33
Figure 09
A suitable fuse must be tted for DC applications.
If the internal fuse is blown, this is most
probably due to a device fault.
In this case, the device should be
checked in the factory.
Connection Cable:
The device is equipped with COMBICON
connectors. This reliable user-friendly connection
method enables quick device connection and safe
isolation of the electrical connection, if required.
Only operate connectors when the power is
switched off.
The following cable cross sections can be connected:
For reliable and safe-to-touch
connection: Strip 7 mm (0.28 in.)
from the connector ends.
6.3. Input (
11
11
, Figure 9)
The 100 - 240 V AC connection is made using screw
connections L and N. The device can be connected to
single-phase AC networks or to two external
conductors for three-phase networks (TN, TT or IT
network according to VDE 0100 T300/IEC364-3) with
nominal voltages of 100 - 240 V AC.
Protecting the Primary Side
The device must be installed according to the
specications of EN 60 950. It must be possible to
switch off the device using a suitable disconnecting
device outside the power supply.
Note that an all-pole disconnecting device must be
provided for two-phase operation using two external
conductors for a three-phase network.
For example, primary side line protection could be
used.
Additional device protection is not required, as an
internal fuse is present.
Recommended Fuse:
Circuit breaker 6 A or 10 A, Characteristic B (or
equivalent).
Solid
[mm
2
]
Flexible
[mm
2
]
AWGTorque
[Nm] [Ib in.]
11
11
Input:
0.2 - 2.5 0.2 - 2.5 25 - 14 0.5 - 0.6 4.4 - 5.3
22
22
Output:
0.2 - 2.5 0.2 - 2.5 25 - 14 0.5 - 0.6 4.4 - 5.3
33
33
Signal:
0.2 - 2.5 0.2 - 2.5 25 - 14 0.5 - 0.6 4.4 - 5.3
7 mm (0.28 in.)