Datasheet

PHOENIX CONTACT page 2 of 8
solid exible torque
[mm
2
]AWG [Nm] [Ib in.]
Input 0.2 - 2.5 0.2 - 2.5 25 - 14 0.5 - 0.6 4.4 - 5.3
Output 0.2 - 2.5 0.2 - 2.5 25 - 14 0.5 - 0.6 4.4 - 5.3
Signal 0.2 - 2.5 0.2 - 2.5 25 - 14 0.5 - 0.6 4.4 - 5.3
Description
Power Supply
Primary switch mode, narrow design
Technical Data
Input Data
1
Nominal input voltage
Input voltage range (current consumption)
Frequency
Current consumption (for nominal values)
Inrush current limiting/I
2
t (+25°C [+77°F])
Mains buffering for a nominal load (typical)
Switch-on time after applying the mains voltage
Transient surge voltage protection
Input fuse, internal
Recommended fuse
Output Data
2
Nominal output voltage U
N
/tolerance
Setting range for the output voltage
Output current during convection cooling
and nominal values POWER BOOST I
BOOST
(t = 2 min., typical)
-25°C to +40°C (-13°F to +104°F)
Nominal output current I
N
-25°C to +60°C (-13°F to +140°F)
Derating
Short-circuit current limit
Startup of capacitive loads
System deviation on: Load change static 10 - 90%
Load change dynamic 10 - 90%
Input voltage change ±10%
Maximum power loss No load/nominal load
Level of efciency (typical)
Response time U
OUT
(10% - 90%)
Residual ripple/switching peaks (20 MHz)
Can be connected in parallel
Internal surge voltage protection
Resistance to return supply
Signal Output Data
DC OK (active) (U
out
> 0.9 x U
N
=
high signal)
LED (U
out
> 21.5 V DC
=
LED permanently on)
MINI-PS-100-240AC/24DC/4
1 AC
U u
Type Order No.
Pcs.
Pkt.
MINI-PS-100-240AC/24DC/4 29 38 83 7
1
100 - 240 V AC (wide range input)
85 - 264 V AC 90 - 350 V DC
45 - 65 Hz 0 Hz
1.3 A (120 V AC)/0.8 A (230 V AC), approximately
< 20 A/< 2.1 A
2
s, typical
> 20 ms (120 V AC)/> 100 ms (230 V AC)
< 0.4 s
Varistor
T3.15 AL 250 V (device protection)
Line protection switch 6 A, 10 A, Characteristic B (EN 60 898)
24 V DC/±1%
22.5 - 28.5 V DC
Up to 6 A (U
out
= 24 V DC)
5A (U
out
= 24 V DC)
4 A (U
out
= 24 V DC)
From +60°C (+140°F), 2.5% per Kelvin
9 A, approximately
Unlimited
< 1%, typical
< 3%, typical
< 0.1%, typical
2.5 W/12 W
> 88% (for 230 V AC and nominal values)
0.3 ms
< 100 mV
pp
(for nominal values)
To increase redundancy and power
Ye s, limited to 35 V DC, approximately
35 V DC
+24 V signal/20 mA, maximum
Green LED
99 mm
(3.898 in.)
67.5 mm
(2.657 in.)
114.5 mm
(4.508 in.)
L (+)
N (–)
DC OK
Power Supply, Primary Switch Mode, Narrow Design – MINI-PS-100-240AC/24DC/4
3. Technical Data
7