Datasheet

https://www.phoenixcontact.com/us/produkte/2938811
Nov 13, 20132/7
Power supply unit-QUINT-PS-100-240AC/12DC/10-2938811
Technical data
Input data
Power failure bypass
> 50 ms (230 V AC)
Input fuse
6.3 A (slow-blow, internal)
Choice of suitable fuses
10 A ... 16 A (Characteristics B, C, D, K)
Output data
Nominal output voltage
12 V DC ±1%
Setting range of the output voltage
11.5 V DC ... 18 V DC
Output current
10 A (nominal value, up to 60°C)
Output current
16 A (with POWER BOOST)
Derating
60 °C ... 70 °C (2.5%/K)
Connection in parallel
Yes, for redundancy and increased capacity
Connection in series
Yes
Max. capacitive load
Unlimited
Residual ripple
< 30 mV
PP
Peak switching voltages nominal load
< 50 mV
PP
(20 MHz)
Maximum power dissipation NO-Load
< 4 W
Power loss nominal load max.
< 22 W
General
Net weight
1.3 kg
Operating voltage display
Green LED
Efficiency
> 84 %
Insulation voltage input/output
2 kV (routine test)
Insulation voltage input/output
4 kV (type test)
Protection class
I, with PE connection
MTBF (IEC 61709, SN 29500)
> 500000 h
Mounting position
horizontal DIN rail NS 35, EN 60715
Assembly instructions
Can be aligned: Horizontally 0 mm, vertically 50 mm
Electromagnetic compatibility
Conformance with EMC directive 89/336/EC
Standard - Safety of transformers
EN 61558-2-17
Standard - Electrical safety
EN 60950-1/VDE 0805 (SELV)
Standard - Electrical safety
EN 61558-2-17
Standard – Electronic equipment for use in electrical power
installations and their assembly into electrical power
installations
EN 50178/VDE 0160 (PELV)
Standard – Safety extra-low voltage
EN 60950-1 (SELV) and EN 60204 (PELV)
Standard - Safe isolation
DIN VDE 0100-410
Standard - Safe isolation
DIN VDE 0106-1010
Standard – Limitation of mains harmonic currents
EN 61000-3-2
Standard - Equipment safety
GS (tested safety)
Information technology equipment - safety (CB scheme)
CB Scheme
UL approvals
UL/C-UL Recognized UL 60950
UL approvals
UL/C-UL listed UL 508