Datasheet
https://www.phoenixcontact.com/us/produkte/2938743
Nov 13, 20132/6
Power supply unit-MINI-PS-100-240AC/2X15DC/1-2938743
Technical data
Input data
AC frequency range
45 Hz ... 65 Hz
Current consumption
0.6 A (120 V AC)
Current consumption
0.4 A (230 V AC)
Current consumption
0.8 A (90 V DC)
Current consumption
0.3 A (350 V DC)
Inrush surge current
< 35 A (typical)
Power failure bypass
> 30 ms (120 V AC)
Power failure bypass
> 150 ms (230 V AC)
Input fuse
2.5 A (slow-blow, internal)
Output data
Nominal output voltage
± 15 V DC ±1%
Output current
2x 1 A (-25 °C ... 60 °C)
Output current
2x 1.5 A (with POWER BOOST, -25°C ... 40°C permanent)
Derating
60 °C ... 70 °C (2.5%/K)
Connection in parallel
Yes, for assembling redundant systems and increasing efficiency
Connection in series
Yes
Current limitation
Approx 4.4 A (in the event of a short circuit)
Control deviation
< 2 % (change in load, static 10% ... 90%)
Control deviation
< 3 % (change in load, dynamic 10% ... 90%)
Control deviation
< 0.1 % (change in input voltage ±10%)
Residual ripple
< 30 mV
PP
(20 MHz)
Peak switching voltages nominal load
< 20 mV
PP
(20 MHz)
Maximum power dissipation NO-Load
2 W
Power loss nominal load max.
8 W
General
Net weight
0.25 kg
Operating voltage display
Green LED
Efficiency
> 80 % (for 230 V AC and nominal values)
Insulation voltage input/output
4 kV (type test)
Insulation voltage input/output
3 kV (Routine test)
Protection class
II (in an enclosed control cabinet)
MTBF (IEC 61709, SN 29500)
> 500000 h (According to EN 29500)
Mounting position
horizontal DIN rail NS 35, EN 60715
Assembly instructions
Can be aligned: Horizontally 0 mm, vertically 50 mm
Electromagnetic compatibility
Conformance with EMC Directive 2004/108/EC
Noise emission
EN 50081-2
Low Voltage Directive
Conformance with LV directive 2006/95/EC
Standard – Electrical equipment of machines
EN 60204
Standard - Electrical safety
EN 60950-1/VDE 0805 (SELV)