Power Supply, Primary Switch Mode, Narrow Design – MINI-PS-100-240AC/5DC/3
6. Installation
Figure 05
5 6 7 8
MINI POWER
L(+)
N(-)
DC
OK
NC
NC
+
+
IN 100-240 V AC
OUT 5 V DC
4.5-5.5
V DC
MINI-PS-100-240AC/5DC/3
Order No.: 29 38 71 4
U
INDUSTRIAL
CONTROL
EQUIPMENT
43KA
LISTED
APPROVALS
u
INFORMATION
TECHNOLOGY
EQUIPMENT
Power Supply
INPUT
OUTPUT
AC:
100-240V
50-60Hz
Range:
85-264V
0.4-0.2A
DC:
90-350V
0.4-0.2A
5V DC
±1%
3A
Read installation instructions
before connecting to mains
www.interface.phoenixcontact.com
TEMPERATURE
- 25 … + 60 °C
- 13 … + 140 °F
2
5
+
––
+
Mounting Removal
Figure 07
6.1. Mounting
The power supply can be snapped onto all DIN rails
according to EN 50022-35. The device must be
mounted horizontally (input terminals facing
downwards).
Installation Dimensions
To ensure sufcient convection, we
recommend the following minimum
spacing be used between modules:
8.0 cm (3.150 in.) for vertical installation
MINI POWER
L(+)
N(-)
DC
OK
NC
NC
+
+
IN 100-240 V AC
OUT 5 V DC
4.5-5.5
V DC
80
99 mm (3.898 in.)
259 mm (10.197 in.)
114.5 mm (4.508 in.)
80
106 mm (4.173 in.)
22.5
Installation depth 106 mm (4.173 in.) (+ DIN
Figure 06
Mounting:
Place the module with the DIN rail guideway on the
top edge
of the DIN rail and then snap it
downwards
.
Removal:
Release the snap-on catch using a screwdriver and
then detach the module from the
bottom edge
of the