Datasheet
https://www.phoenixcontact.com/us/produkte/2938617
Nov 14, 20132/9
Power supply unit-QUINT-PS-3X400-500AC/24DC/10-2938617
Technical data
Input data
Input voltage range AC
3x 320 V AC ... 575 V AC (for all three phases)
Input voltage range DC
450 V DC ... 800 V DC
AC frequency range
45 Hz ... 65 Hz
Frequency range DC
0 Hz
Current consumption
approx. 3x 0.63 A (400 V AC)
Current consumption
3x 0.57 A (480 V AC)
Nominal power consumption
240 W
Inrush surge current
< 15 A (typical)
Power failure bypass
> 40 ms (400 V AC)
Power failure bypass
> 40 ms (480 V AC)
Input fuse
5 A (slow-blow, internal)
Choice of suitable fuses
3x 6 A ... 16 A (Characteristics B, C, D, K)
Type of protection
Transient surge protection
Protective circuit/component
Varistor
Output data
Nominal output voltage
24 V DC ±1%
Setting range of the output voltage
22.5 V ... 28.5 V
Output current
10 A (up to 60°C)
Output current
15 A (with POWER BOOST)
Derating
60 °C ... 70 °C (2.5%/K)
Connection in parallel
Yes, for redundancy and increased capacity
Connection in series
Yes
Current limitation
ca. I
BOOST
= 15 A (for short-circuit)
Control deviation
< 1 % (change in load, static 10% ... 90%)
Control deviation
< 2 % (change in load, dynamic 10% ... 90%)
Control deviation
< 0.1 % (change in input voltage ±10%)
Residual ripple
< 20 mV
PP
(with nominal values)
Peak switching voltages nominal load
< 100 mV
PP
(20 MHz)
Maximum power dissipation NO-Load
< 4 W
Power loss nominal load max.
< 28 W
General
Net weight
1.1 kg
Operating voltage display
Green LED
Efficiency
> 90 %
Insulation voltage input/output
4 kV AC (type test)
Insulation voltage input/output
2 kV AC (routine test)
Protection class
I, with PE connection
MTBF (IEC 61709, SN 29500)
> 500000 h
Mounting position
horizontal DIN rail NS 35, EN 60715
Assembly instructions
Can be aligned: Horizontally 0 mm, vertically 50 mm