Datasheet
https://www.phoenixcontact.com/us/produkte/2938604
Nov 14, 20132/9
Power supply unit-QUINT-PS-100-240AC/24DC/10-2938604
Technical data
Input data
Input voltage range AC
85 V AC ... 264 V AC
Input voltage range DC
90 V DC ... 350 V DC
AC frequency range
45 Hz ... 65 Hz
Frequency range DC
0 Hz
Current consumption
approx. 2.34 A (120 V AC)
Current consumption
approx. 1.2 A (230 V AC)
Nominal power consumption
240 W
Inrush surge current
< 15 A (typical)
Power failure bypass
> 50 ms (120 V AC)
Power failure bypass
> 50 ms (230 V AC)
Input fuse
6.3 A (slow-blow, internal)
Choice of suitable fuses
10 A ... 16 A (Characteristics B, C, D, K)
Type of protection
Transient surge protection
Protective circuit/component
Varistor
Output data
Nominal output voltage
24 V DC ±1%
Setting range of the output voltage
22.5 V DC ... 28.5 V DC
Output current
10 A (up to 60°C)
Output current
15 A (with POWER BOOST)
Derating
60 °C ... 70 °C (2.5%/K)
Connection in parallel
Yes, for redundancy and increased capacity
Connection in series
Yes
Max. capacitive load
Unlimited
Current limitation
ca. I
BOOST
= 15 A (for short-circuit)
Control deviation
< 1 % (change in load, static 10% ... 90%)
Control deviation
< 2 % (change in load, dynamic 10% ... 90%)
Control deviation
< 0.1 % (change in input voltage ±10%)
Residual ripple
< 60 mV
PP
(with nominal values)
Peak switching voltages nominal load
< 60 mV
PP
(20 MHz)
Maximum power dissipation NO-Load
< 2 W
Power loss nominal load max.
< 24 W
General
Net weight
1.3 kg
Operating voltage display
Green LED
Efficiency
> 91 %
Insulation voltage input/output
4 kV AC (type test)
Insulation voltage input/output
2 kV AC (routine test)
Protection class
I, with PE connection
MTBF (IEC 61709, SN 29500)
> 500000 h
Mounting position
horizontal DIN rail NS 35, EN 60715