Datasheet
https://www.phoenixcontact.com/us/produkte/2938248
Nov 10, 20132/7
Power supply unit-QUINT-PS-100-240AC/48DC/10-2938248
Technical data
Input data
Input voltage range AC
85 V AC ... 264 V AC
Input voltage range DC
90 V DC ... 350 V DC
AC frequency range
45 Hz ... 65 Hz
Frequency range DC
0 Hz
Current consumption
approx. 4.76 A (120 V AC)
Current consumption
2.3 A (230 V AC)
Nominal power consumption
480 W
Inrush surge current
< 15 A (3.2 A
2
s)
Power failure bypass
> 30 ms (120 V AC)
Power failure bypass
> 35 ms (230 V AC)
Input fuse
12 A (slow-blow, internal)
Type of protection
Transient surge protection
Protective circuit/component
Varistor
Output data
Nominal output voltage
48 V DC ±1%
Setting range of the output voltage
30 V DC ... 56 V DC
Output current
10 A (nominal value, up to 60°C)
Output current
13 A (with POWER BOOST)
Derating
60 °C (2.5%/K)
Connection in parallel
Yes, for redundancy and increased capacity
Connection in series
Yes
Max. capacitive load
Unlimited
Control deviation
< 1 % (change in load, static 10% ... 90%)
Control deviation
< 5 % (change in load, dynamic 10% ... 90%)
Control deviation
< 0.1 % (change in input voltage ±10%)
Residual ripple
< 20 mV
PP
(with nominal values)
Peak switching voltages nominal load
< 50 mV
PP
Maximum power dissipation NO-Load
< 5 W
Power loss nominal load max.
< 56 W
General
Net weight
2.5 kg
Efficiency
> 90 %
Insulation voltage input/output
4 kV AC (type test)
Insulation voltage input/output
2 kV AC (routine test)
Protection class
I, with PE connection
MTBF (IEC 61709, SN 29500)
> 500000 h
Mounting position
horizontal DIN rail NS 35, EN 60715
Assembly instructions
Can be aligned: Horizontally 0 mm, vertically 50 mm
Electromagnetic compatibility
Conformance with EMC directive 89/336/EC
Standard – Electrical equipment of machines
EN 60204