Datasheet

https://www.phoenixcontact.com/us/produkte/2938219
Nov 9, 20132/6
Power supply unit-QUINT-PS-3X400-500AC/48DC/10-2938219
Technical data
Input data
Power failure bypass
> 25 ms (400 V AC)
Power failure bypass
> 30 ms (480 V AC)
Type of protection
Transient surge protection
Protective circuit/component
Varistor
Output data
Nominal output voltage
48 V DC ±1%
Setting range of the output voltage
30 V DC ... 56 V DC (> 48 V constant capacity)
Output current
10 A (-25 °C ... 60 °C)
Output current
13 A (with POWER BOOST, -25°C ... 40°C permanent)
Derating
60 °C ... 70 °C (2.5%/K)
Connection in parallel
Yes, for redundancy and increased capacity
Connection in series
Yes
Residual ripple
< 20 mV
PP
Peak switching voltages nominal load
< 140 mV
PP
(20 MHz)
Maximum power dissipation NO-Load
10 W
Power loss nominal load max.
45 W
General
Net weight
2.3 kg
Efficiency
> 90 % (for 230 V AC and nominal values)
Insulation voltage input/output
3 kV (type test)
Insulation voltage input/output
1.5 kV (routine test)
Protection class
I, with PE connection
MTBF (IEC 61709, SN 29500)
> 500000 h
Mounting position
horizontal DIN rail NS 35, EN 60715
Assembly instructions
Can be aligned: Horizontally 0 mm, vertically 50 mm
Electromagnetic compatibility
Conformance with EMC Directive 2004/108/EC
Noise emission
EN 50081-2
Low Voltage Directive
Conformance with LV directive 2006/95/EC
Standard - Safety of transformers
EN 61558-2-17
Standard - Electrical safety
EN 60950-1/VDE 0805 (SELV)
Standard - Electrical safety
EN 61558-2-17
Standard – Electronic equipment for use in electrical power
installations and their assembly into electrical power
installations
EN 50178/VDE 0160 (PELV)
Standard - Safe isolation
DIN VDE 0100-410
Standard - Safe isolation
DIN VDE 0106-1010
Standard – Limitation of mains harmonic currents
EN 61000-3-2
Standard - Equipment safety
GS (tested safety)
Information technology equipment - safety (CB scheme)
CB Scheme
UL approvals
UL/C-UL listed UL 508
UL approvals
UL/C-UL Recognized UL 60950